Cast iron drainage for aggressive effluents
Agilium® Plus is a lightweight cast iron drainage system compliant with the EN 877 standard, tested against more than 40 aggressive effluents across the pH 1-13 range. It withstands a continuous
daily exposure temperature of the effluent up to 70°C.
Specified for hospitals and clinics, laboratories, industrial laundries, commercial kitchens and car parks.
Applications
Agilium® Plus is specified where discharge is chemically loaded or hot. The five sectors below correspond to the effluent families in our test programme (see table below).

Hospitals and clinics
Hospital drainage carries the most aggressive disinfectants in daily use -peracetic acid, hydrogen peroxide, sodium hypochlorite, often at elevated temperature. Endoscopy, sterilisation and haemodialysis runs are the critical ones.

Laboratories
Laboratory networks rarely carry a single chemical family. Concentrated acids, bases and solvents may discharge into the same run, which is why certification across the whole pH 1-13 range matters more than any single value.

Industrial laundries
Sustained high-temperature discharge combined with alkaline detergents, surfactants and bleach, circulating through the network at up to 80 °C.

Commercial kitchens
Hot grease, food-grade fatty effluents and aggressive cleaning agents, with dishwasher and steam discharge frequently reaching 93 °C on a non-continuous basis.

Car parks
Hydrocarbons, fuel and oil residues, de-icing salts and the runoff that carries them, in enclosed and underground structures where replacing a network is costly.
Agilium® Plus is a cast iron pipe compliant with EN 877, designed for buildings whose discharge is chemically aggressive or hot. Its distinguishing feature is a two-component epoxy interior coating applied in two layers, 250 µm average dry film thickness, which allows the network to carry acids, bases, disinfectants and solvents that degrade conventional linings.
For a design office, the practical consequence is that a single material can be specified across a mixed-discharge building: theatre and endoscopy drainage, laboratory benches, laundry, catering and car park runs, without switching to stainless steel or plastic at each change of effluent. Pipes are available from DN 50 to DN 300 in 3 m lengths and are compatible with our Pam Global® Plus fittings.

30% lighter
A DN 100 three-metre pipe weighs 17.6 kg, on average 30% less than the standard Pam Global® Plus range. Lighter sections mean single-operator handling on most diameters, fewer lifting constraints in occupied hospital buildings, and reduced load on fixings and structure — a point worth carrying into the specification rather than leaving to the installer to discover.

Easy handling on a DN 100 length.
Specification Toolbox
On demand to your sales manager. For project-specific work (bill of quantities, acoustic or fire justification, bespoke fittings) our technical team responds directly.
Agilium® Plus brochure (PDF, 8 pages)Full product presentation, effluent tables, technical data and references.
Specification text / CCTPReady-to-use clause for your tender documents, available in 9 languages. Select yours below.
Chemical resistance table (Excel)All tested effluents with dilution, pH, temperature and result. Ask your sales contact!
BIM libraryGeneric cast iron EN 877 library and Plus range EN 877 library.
Project estimationSend your drawings in DWG or PDF to tc@pambuilding.com; we return a bill of quantities with references.
Specification text (CCTP) — Agilium® Plus
Choose your language to display the full specification clause, then copy it straight into your tender documents.
Select a language above to display the Agilium® Plus specification text.
Chemical resistance: look up your effluent
Agilium® Plus was tested against more than 40 effluents in accordance with EN ISO 2812-1. Samples were immersed for 120 days, then assessed to EN 877: blistering rated to EN ISO 4628-2, rusting area to ISO 4628-3, and coating adhesion by cross-cut test to EN ISO 2409. Search below to see the maximum concentration and temperature certified for each substance.

Type at least 2 characters of a substance or product name, or choose an application, to check its compatibility with Agilium® Plus.
| Category | Description | Solution / Medium | Dilution | pH | Temp. (°C) | Plus Range |
|---|
Projects where the Plus range is installed
The Plus range is specified internationally on healthcare, hospitality and stadium projects.




Also installed: Moulay Abdellah and Moulay El Hassan Stadiums (World Cup 2030), Rabat, Morocco; Royal Mansour Hotel, Marrakech. See all project references →
Frequently asked questions
What effluents is Agilium® Plus resistant to? +
What temperature can Agilium® Plus withstand? +
Which standards apply to Agilium® Plus? +
How does Agilium® Plus compare with stainless steel or HDPE? +
Is an expansion joint required? +
Which fittings and couplings should be specified? +
What discharge and applications is Agilium® Plus intended for? +
Talk to a technical expert
Send us a drawing, an effluent list, or a question about acoustics, fire protection or sizing. Our technical team answers design offices directly, and can return a bill of quantities with the references to order.